FAULT: No reply zone: 123 address: 01
technical number 000025
"...alarm text..."
2021-04-03 15:22
FAULT: No reply zone: 123 address: 03
technical number 000027
"...alarm text..."
2021-04-07 09:25
Number of faults in system: 5
Menu
To acknowledge the faults shown:
Login, according to chapter "Access Levels", page 42.
•
Use menu H6 (access level 2A) to acknowledge fault, see chapter "FAULT
•
Acknowledge (H6)", page 146. Menu H6 is a list showing a maximum of 300 faults
(not acknowledged faults and/or acknowledged but not serviced / corrected faults).
•
All faults must be individually acknowledged one by one using the key pad button
, Use or to scroll.
When a fault is corrected before it has been acknowledged, the text "Serviced" is
•
added after the time, still has to be acknowledged to remove from the display.
When a fault is corrected / serviced and acknowledged, it will disappear from the
•
list (H6).
When all faults have been acknowledged, the output for routing equipment (Fault
•
TX) will not reset and the LED for Routing equipment "Fault TX activated"
remains activated until there are no faults in the system.
Whilst faults still not corrected in the system (Acknowledged faults corrected or not
•
corrected), the LED Fault / Disablements "General fault" will be lit and general
fault (and maybe general charger fault) output(s) are activated. The fault relay also
stays energised.
•
Faults, corrected faults and acknowledged faults are shown in the General event
log (menu H4/U6).
/Serviced
/Acknowledge
85
Operation Manual
FT1020G3 Rev 2.10.4