Panasonic Brooks FireTracker FT1020G3 Operation Manual page 111

Hide thumbs Also See for Brooks FireTracker FT1020G3:
Table of Contents

Advertisement

After 15 minutes
or
"ESC" and
"Escape
menu"
"Menu"
Log in (see
above), select
menu H1,
step down to this view.
"↵"
Press "↵" (i.e. select "No") to bypass the routing equipment test If so, the monthly test is
completed. The routing equipment test is always carried out from the ASE.
"
"
Note 1: During the test, the following information will be shown in all other FDCIE displays:
Zone 001, 002, 003 or 004 in test mode
Note 2: If an alarm point e.g. a manual call point is in alarm state when the test mode is
terminated, there will be a fire alarm activated.
Note 3: When the "Fire door closing" function is used, the fire door will be closed when the
detectors controlling the door are tested, in test mode.
Zone 001 in test mode
Zone 002 in test mode
Zone 003 in test mode
Zone 004 in test mode
(Note: See chapter "Information Area Priority
Order", page 22 regarding priority order.)
Zones in test mode:
001 002 003 004
End test: ↵
Please wait....
Test of routing equipment?
Monthly test is completed!
Press
▒▒▒ menu
H1 Perform monthly test
H2 .....
No
Yes
111
Operation Manual
FT1020G3 Rev 2.10.4
You are logged out
but the zone(s) are
still in test mode.
Press "↵" to end test.
The LED "Test mode"
is turned OFF.
Scroll to another
menu or press
"ESC".