Explanation Of Restart Codes; During Restart - Panasonic Brooks FireTracker FT1020G3 Operation Manual

Hide thumbs Also See for Brooks FireTracker FT1020G3:
Table of Contents

Advertisement

Automatically (by the S/W itself) S/W watchdog.
Automatically due to external disturbance.
Note: During a restart, the fault output (relay) for the Fault TX will be "activated" for few
seconds, the supervised 24 V
programmed as normally high will be low for few seconds.
21.2.1

Explanation of Restart Codes

Code 00 displays after manual power on/off or S/W download.
Code 03 will display after a normal restart.
Code 13 is always followed by an address, to be noted.
Code 25 displays after download of SSD and automatic restart.
Code 50 & 53 will display only if the FDCIE has an MMI board.
Note: Code 00 – 49 = Main board restart. Some data might be lost, see above.
Code 50 – 99 = MMI board restart. No data is lost.
21.3

During Restart

During "restart", no fire alarms will be activated and the following is shown on the display:
And after few seconds (the control panel starts the normal restart procedures else see
Memory fault below):
Booting......
A fault will be generated, the buzzer will sound and the following text message will be
shown in the display:
FAULT: Restart Control Unit nn, code xx,
address yyyyyy
Regarding code xx and address yyyyyy, see Table 18 above.
This fault is also indicated by LEDs Routing equipment "Fault TX activated" and Fault /
Disablements "General fault".
After the fault is acknowledged (via menu H6 or EBLWin), the LEDs will be turned OFF, if
no other faults exist in the system.
After any restart, if any units were disabled before restart, an individual disablement for
these units should be done.
FFD, WASV
SSD, S/W, SSW
FFD, WASV
SSD, S/W, SSW
outputs S0-S3 will not be supervised and S0-S3
DC
108
Operation Manual
FT1020G3 Rev 2.10.4
13
01, 02 alt.
04-12