29.3

Clear Weekly Average (H8/S3)

Valid only for 430x, 4400 and 4401 sensors in NORMAL mode.
If a sensor (analogue smoke detector) is replaced without having generated SERVICE
signal, its week average sensor value has to be cleared and set to the default value (i.e.
"1" = 0.1 %/m), otherwise the new / clean sensor will inherit the old sensor's value. It is
possible to clear the week average sensor value for each sensor individually via this menu.
Note: First, replace the sensor and then clear the week average value as soon as possible.
Authorised service personnel only, must do this. Using the function incorrectly may cause
nuisance fire alarms.
The first week average sensor value (after clearing) will be calculated within one hour, then
each week.
Action
"Menu"
Scroll to menu H8.
"↲"
Scroll to menu S3.
"↲"
Write the zone and
address numbers, (e.g.
001 and 01).
"↲"
"ESC"
Text in display
H8 Maintenance
S1 Dis- / Re-connect loop / zone line input
S2 Acknowledge SERVICE signal
S3 Clear weekly average
S4 Test of alarm devices
S5 Safe shut down of control unit
S6 Activate address in alarm mode
S7 Synchronize the control units
S8 Activate / Reset outputs
S3 Clear weekly average
(press ↵)
Clear weekly average zone: 000 address: 00
Weekly average zone 001 address 01 cleared
S3 Clear weekly average
154
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
Write the required zone
and address and press
"↲".
Continue as above or
scroll to another menu
or press "ESC".

Advertisement