31.7. ACTIVATE ADDRESS SETTING MODE FOR DU (H5/A7)

This function can be used by commissioning / service engineer to activate the address setting mode in the following Display Units
connected to the c.i.e.:
This can also be done via jumper "J4" inside the D.U. respectively.
Ext. Presentation unit
Alert Annunciation units
Fire Brigade Panels
General Control Panel
A specific unit or all units connected to one c.i.e. can be activated for address setting.
The units have to be in operation and in quiescent condition, which means the units have to have an ad-
dress already.
a) Log on to the c.i.e.
b) Navigate to menu A7.
c) Write control unit number and the display unit address and press
OR
d) Press
to select All and press
Address setting mode for display unit 00,
control unit 00 activated
e) Edit the address in each display unit respectively.
f) To exit the menu press
. (All display units in the selected control unit.)
or ESC.
.