6.5

Wiring

Wiring of terminal block for module power supply and FG

Wiring of spring clamp terminal block
■Tightening torque
Tighten the terminal block mounting screw within the following specified torque range.
Tightening the screw too much may damage the module case.
Screw type
Terminal block mounting screw (M2.5 screw)
■Wire to be used
The following table describes the wire to be connected to the terminal block for module power supply and FG.
Diameter
22 to 16 AWG
■Applicable solderless terminal
The following table lists the applicable solderless terminal.
Product name
Model name
Bar solderless
AI 0.34-8TQ
terminal
AI 0.5-8WH, AI 0.5-10WH
AI 0.75-8GY, AI 0.75-10GY
AI 1-8RD, AI 1-10RD
AI 1.5-8BK, AI 1.5-10BK
TE 0.5-8, TE 0.5-10
TE 0.75-8, TE 0.75-10
TE 1.0-8, TE 1.0-10
TE 1.5-8, TE 1.5-10
*1 Use a bar solderless terminal tool whose manufacturer is the same as that of the bar solderless terminal used.
■Installing or removing the terminal block
To remove the terminal block, loosen the terminal block mounting screw with a flathead screwdriver.
To install the terminal block, tighten the terminal block mounting screw with a flathead screwdriver.
Failure to secure the terminal block may cause drop, short circuit, or malfunction.
Type
Stranded
Applicable wire size
0.34
0.5
0.75
1.0
1.5
0.3 to 0.5
0.75
1.0
1.5
Tightening torque range
0.2 to 0.3Nm
Material
Copper
Bar solderless terminal
*1
tool
CRIMPFOX6
NH-79
6 INSTALLATION AND WIRING
Temperature rating
75 or more
Contact
PHOENIX CONTACT GmbH & Co. KG
NICHIFU Co., Ltd.
6.5 Wiring
6