3.5.2

Output Items (OUTA)

When the OUTA tab is selected, you can use the output display settings to configure the following items.
Setting item Bank Setting value/default value
Out target
Y
Select the area or calculation to set as the output target.
Area1
Area2
Area3
Area4
Calc1
Calc2
20mA
Y
Set the upper limit of analog output.
-31.767 to +32.767 [+25.000]
4mA
Y
Set the lower limit of analog output.
-32.767 to +31.767 [-25.000]
Tips
Set the "20mA" and "4mA" input values so that they meet the following conditions.
If the following conditions are not met, analog output will not be performed correctly.
• The "20mA" input value must be greater than the "4mA" input value.
• The difference between the "20mA" and "4mA" input values must be 1.000 or more.
Reference
For details on the output display settings, see "5.8 Output Settings."
Ramco National
The measured result of area 1 will be output.
The measured result of area 2 will be output.
The measured result of area 3 will be output.
The measured result of area 4 will be output.
The result of calculation 1 will be output.
The result of calculation 2 will be output.
* The unit varies depending on the measurement function.
* The unit varies depending on the measurement function.