5.10.9 Connecting the equipotential bonding
Fig. 23: Equipotential bonding
terminal
NOTE
This chapter only applies to charging systems that are equipped with a surge protection device type
1/2/3 - DIN EN 61643-11 and whose use is prescribed by local directives.
•
See chapter 3.3 Technical specifications, page 16.
2022-11
1.
Route the equipotential bonding conductor up to the
terminal (1), cut to length and strip the sheath to a
1
length of approx. 70 mm.
2.
Strip the wires 18 mm.
3.
Connect the line on the external wiring side and
ensure that the terminal screws are tightened (M = 2.0
- 4.0 Nm).
A01Axxxxxx.xx | 04
45