5.3 Notes on electrical installation
DANGER
Danger due to electric current
Touching live parts will result in electric shock with serious injury or death.
•
Work on electrical components may only be carried out by a qualified electrician and in
accordance with electrical engineering rules.
•
Ensure they are de-energised and take suitable protective measures.
•
For safe disconnection during installation work, disconnect the charging system from the power
supply.
–
Switch off the circuit breaker or main switch.
Observe the national legal requirements and regulations during electrical installation. In Germany,
these include the following safety requirements:
•
DIN VDE 0100-100
•
DGUV Regulation 1
•
DGUV Regulation 3+4
•
TRBS 1201
NOTE
The protection technology required for the charging point (MCB) is not installed within the charging
system.
•
Suitable protection technology must be installed in the upstream sub-distribution.
•
The MCB must be selected with a type C tripping characteristic.
•
See chapter 3.3 Technical specifications, page 16.
NOTE
The residual current circuit breaker (RCCB) required for the charging point is not installed within the
charging system.
•
Suitable protection technology must be installed in the upstream sub-distribution.
•
The RCCB must comply with the characteristic 40 A/0.03 A, type A.
•
See chapter 3.3 Technical specifications, page 16.