5.3 Notes on electrical installation

DANGER
Danger due to electric current
Touching live parts will result in electric shock with serious injury or death.
Work on electrical components may only be carried out by a qualified electrician and in
accordance with electrical engineering rules.
Ensure they are de-energised and take suitable protective measures.
For safe disconnection during installation work, disconnect the charging system from the power
supply.
Switch off the circuit breaker or main switch.
Observe the national legal requirements and regulations during electrical installation. In Germany,
these include the following safety requirements:
DIN VDE 0100-100
DGUV Regulation 1
DGUV Regulation 3+4
TRBS 1201
NOTE
The protection technology required for the charging point (MCB) is not installed within the charging
system.
Suitable protection technology must be installed in the upstream sub-distribution.
The MCB must be selected with a type C tripping characteristic.
See chapter 3.3 Technical specifications, page 16.
NOTE
The residual current circuit breaker (RCCB) required for the charging point is not installed within the
charging system.
Suitable protection technology must be installed in the upstream sub-distribution.
The RCCB must comply with the characteristic 40 A/0.03 A, type A.
See chapter 3.3 Technical specifications, page 16.