5.10 Installation and connection
ATTENTION
Damage to the unit
Vehicles unintentionally running into the unit can cause damage.
•
Select the installation site in such a way that damage due to vehicles unintentionally running
into the unit is prevented.
•
If damage cannot be ruled out, suitable protective measures must be taken.
5.10.1 Wall mounting
Installation requirements
•
Wall with sufficient load-bearing capacity, e.g. masonry or concrete construction
•
Smooth supporting surface on the wall
•
At least 600 mm lateral free space around the charging system for heat dissipation.
•
At least 150 mm distance to the building ceiling
•
At least 900 mm from the top of the ground or the soil.
6
3
4
5
2
Fig. 15: Connection box
Installation is carried out on walls with a suitable load-bearing capacity.
The charging system is then mounted using the fixing material included in the scope of delivery and
finally installed.
The exact dimensions and weights of the charging system can be found in the corresponding
documents in chapter 13.1 Housing dimensions, page 100.
2022-11
(1)
Connection box
(2)
Spirit level
(3)
Through terminal outer conductor
(4)
Through terminal neutral conductor
(5)
Through terminal protective earth
(6)
Plastic top-hat rail clips
1
A01Axxxxxx.xx | 04
37