3.2.3 Grounding
Always ground the X1 series unit. (The level of grounding resistance should be 100 or less.)
• Independent grounding must be used for the unit.
• Use AWG20 to AWG14 wire for the grounding cable.
• Set the grounding point near the unit to reduce the length of grounding cables.
• The signal ground (SG) and frame ground (FG) are connected inside the X1 series unit.
Independent grounding (best)
X1 series
Other
unit
devices
Grounding
resistance:
100 or less
Shared grounding (good)
X1 series
Other
unit
devices
Grounding
resistance:
100 or less
Cross grounding (prohibited)
X1 series
Other
unit
devices
3.2
Power Supply
1
2
3
4
5
6
7
8
9
10
3-5