5.4.19 Handling Data Changed in Local Mode

The following items set in the screen program can be changed in Local mode on the X1 series unit.
Item
Setting in Local Mode *1
Network table
LAN Setting
LAN2 Setting
Service Port
Time-Out
E-Mail Setting
[E-Mail Setting]
Communication Parameter
[Comm. Setting]
Buzzer Setting
[System Setting]
Backlight Setting
Serial Setting
User Settings
[User Settings]
*1
Settings can be made to prohibit changes in Local mode. For details, refer to
Settings Changed in Local Mode
• The screen program will not be overwritten. In any case where the X1 series unit is replaced such as due to a failure, the settings need
to be changed again in Local mode.
• The settings changed in Local mode are retained even if the power to the X1 series unit is turned off.
• If a setting is changed in Local mode, the Local mode setting takes priority.
To restore the settings of the screen program, press the [Restore Screen Data Settings] switch on the respective Local mode screen.
• When writing the screen program into the X1 series unit using V-SFT version 6, you can select whether to retain or clear the settings
changed on the unit (INI file).
<How to clear the INI file using V-SFT version 6>
1) Cable connection
Connect the X1 series unit to a computer using a LAN cable.
2) Starting V-SFT version 6
Start V-SFT version 6 on the computer and open the screen program.
3) Displaying the [Transfer] window
Click [Transfer]  [Download]. The [Transfer] window is displayed.
4) Selecting data to transfer
Select [Screen Data] for [Transfer Data].
Check the [Clear IniFile] in the [Option] window and click [OK].
5) Start downloading to the X1 series unit
Click [PC ]. Screen program transfer starts.
When the following dialog is displayed, click [Yes].
[System Setting]  [Ethernet Communication]  [Network Table]
[System Setting]  [Ethernet Communication]  [Local Port]
(page
5-30)
[System Setting]  [Ethernet Communication]  [E-Mail]
(page
5-36)
[System Setting]  [Hardware Setting]  PLC1 to PLC8
(page
5-42)
[System Setting]  [Unit Setting]  [Buzzer]/[Backlight]
None
(page
5-57)
Security
[System Setting]  [Other]  [Security Setting]
page
Setting in V-SFT Version 6
5-64.