6 Errors
Error Numbers
Check the contents of the error (= error number) according to the item name and sub-item number, and remove the error.
Error: xxx (Item name: Sub-item number)
Error No.
3
The screen program version does not match the X1 series unit
system program version.
11
The PLC model set in the screen program does not match the
I/F driver.
13
The I/F driver version does not match the version of the X1
series unit system program.
15
The interface language on MONITOUCH does not match the
language set in the screen program.
20
The maximum capacity of the logging server has been
exceeded.
22
The logging/alarm block number specified for a trend or
alarm part has not been set.
27*
An error was found in the logging server or alarm server.
36*
ITEM error
38*
Component error
41*
Recognition flag error
42*
Function ITEM error
44*
Group ITEM end error
46
An unavailable device memory address is set or the available
device memory range is exceeded.
47
IDs of the items having setting limitations in the screen library
are duplicated on a screen.
49*
Group ITEM error
50*
Link ITEM error
52
The overlap ID is incorrect and must be a value from "0" to "9".
53
An overlap library number with no part registered is specified
in the call-overlap setting.
56*
Graphic undefined command error
59*
Switch function error
61*
Statistic graph % display No. exceeding
64*
Data display element No. error
65
The scale or graph is not set correctly in the trend part
settings.
66*
Internal circle radius is "0".
67*
The number of points to display is equal to or smaller than
zero.
69
A pattern or frame larger than the screen size has been
specified.
74
An animation part is placed in the area other than the base
screen (screen library, etc.).
77*
Expanded graphic ITEM error
78*
Expanded function ITEM error
80*
Macro: Undefined command error
81
Macro: The numbers of FOR and NEXT commands are not the
same. FOR-NEXT commands are nested beyond 8 levels.
82
Macro: There are two different commands for the same label
number.
83
Macro: There is no destination label for the jump.
84
Macro: Incorrect use of device memory
6-2
Contents
Screen number: Refer to
page
6-4.
Error location
Error number: Refer to the table below.
Update the X1 app version.
If the problem persists, check the editor version and the system program
version of the X1 series unit, and contact your local distributor.
Check the I/F driver version and the system program version of the X1 series
unit, and contact your local distributor.
Check the MONITOUCH model and the language set in the created
program.
The capacity of DRAM specified under [Internal Storage Setting] in the
[Logging Server] window has exceeded the maximum available capacity.
Reduce the number set for [Number of Data to Save].
Select [System Setting]  [Logging Server] or [Alarm Server], and set the
corresponding block number again.
Contact your local distributor.
Check the device memory setting.
For a system with an Ethernet connection, check the settings at [Hardware
Setting]  [Target Settings]  [PLC Table].
Check the IDs and keep them unique.
Contact your local distributor.
Check the overlap ID and set correctly.
Specify an overlap library number with a part registered.
Contact your local distributor.
Correct the settings for [Scale Max. Value] and [Scale Min. Value] or [Graph
Max. Value] and [Graph Min. Value] in the [Detail] window.
Contact your local distributor.
Re-set the pattern or frame.
Place the animation part on the base screen.
Contact your local distributor.
Contact your local distributor.
Correct the FOR-NEXT commands.
Macro: Re-set the label.
Macro: Change or set the destination label.
Change the macro command.
Solution