Fuji Electric MONITOUCH X1 Series Hardware Specifications page 124

Table of Contents

Advertisement

If a password has been registered in the [Prohibition Cancel Setting] window in V-SFT version 6, the list of password-protected settings is
displayed in the [Screen Data Information] tab window of the System Information screen in Local mode.
To cancel all prohibition settings at once, follow the procedure described below.
1. Press [System Information] in the menu icons and open the [Screen Data Information] tab window on the System Information screen.
Press anywhere on the area enclosed in the following figure. Then the system keyboard appears. Enter the password.
2. Press the [Apply] switch. The following confirmation dialog appears. Press the [OK] switch.
All items that were prohibited in Local mode become unprotected.
3. To validate the Local-mode prohibition setting again, open the [System Information]  [Screen Data Information] tab window, and
press the [Relock] switch.
The following confirmation dialog appears. Press [OK].
* The prohibition setting is also validated again after the power is turned off and back on again or a screen program with Local-mode
prohibition settings is transferred.
Notes
• When a screen program is transferred without selecting the [Prohibit Setting] checkbox in the [System Setting]  [Unit Setting] 
[Local Mode]  [Local Mode Prohibition Setting] tab window in V-SFT version 6, the Local-mode prohibition setting becomes invalid
(cancelled).
5.4
Local Mode
1
2
3
4
5
6
7
8
9
10
5-65

Advertisement

Table of Contents
loading