Chapter 3 Specifications; General Specifications - Mitsubishi Electric NZ2GF2B-60TCTT4 User Manual

Cc-link ie field network temperature control module
Table of Contents

Advertisement

CHAPTER 3
This chapter describes the specifications of the temperature control module.
3.1

General Specifications

Item
Operating ambient
0 to 55
temperature
Storage ambient
-25 to 75
temperature
Operating ambient
humidity
5 to 95%RF, non-condensing
Storage ambient
humidity
Compliant with JIS
Vibration resistance
B 3502 and IEC
61131-2
Shock resistance
Compliant with JIS B 3502 and IEC 61131-2 (147m/s
Operating
No corrosive gases
atmosphere
*1
0 to 2000m
Operating altitude
Installation location
Inside a control panel
Overvoltage
II or less
*3
category
*4
2 or less
Pollution degree
Equipment class
Class I
*1
Do not use or store the temperature control module under pressure higher than the atmospheric pressure of altitude 0m.
Doing so may cause malfunction. When using the temperature control module under pressure, please consult your local
Mitsubishi representative.
*2
If the environment satisfies the operating ambient temperature, operating ambient humidity and other conditions, the
module can be used even outside the control panel.
*3
This indicates the section of the power supply to which the equipment is assumed to be connected between the public
electrical power distribution network and the machinery within premises. Category II applies to equipment for which
electrical power is supplied from fixed facilities. The surge voltage withstand level for the equipment with the rated
voltage of 300V or less is 2500V.
*4
This index indicates the degree to which conductive material is generated in terms of the environment in which the
equipment is used. Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by
condensing must be expected occasionally.
To use the temperature control module complying with the EMC Directive, refer to the following.
Page 368, Appendix 4
SPECIFICATIONS
Frequency
5 to 8.4Hz
Under intermittent
vibration
8.4 to 150Hz
5 to 8.4Hz
Under continuous
vibration
8.4 to 150Hz
2
, 3 times each in X, Y, and Z directions)
*2
Specifications
Constant
Half amplitude
acceleration
3.5mm
2
9.8m/s
1.75mm
2
4.9m/s

CHAPTER 3 SPECIFICATIONS

Number of sweeps
10 times each in X,
Y, and Z directions
33
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2gf2b-60tcrt4

Table of Contents