(34)Temperature rise completion soak time setting (address: 1E3H)
Set the time for CH Temperature rise judgment flag (RX1C to RX1F) (Page 290, Appendix 1.1 (11)) to turn
on after the completion of temperature rise.
(a) Setting range
The setting range is 0 to 3600 (min).
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default value is set to 0 (min).
(35)Sensor correction function selection (address: 1E4H)
Select the method of the sensor correction for each channel.
b15
For details on the sensor correction function, refer to the following.
Page 132, Section 8.1.5
(a) Setting range
• 0H: Normal sensor correction (one-point correction)
• 1H: Sensor two-point correction
(b) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(c) Default value
Default value is set to Normal sensor correction (one-point correction) (0H).
to
b12
b11
to
b8
b7
CH4
CH3
Common
to
b4
b3
to
b0
CH2
CH1
APPENDICES
A
Standard
Heating-cooling
341