(2) Procedures
(a) Parameter settings
1.
Display the CC IE Field Configuration window.
• When the master/local module is the QJ71GF11-T2
Project window  [Parameter]  [Network Parameter]  [Ethernet/CC IE/MELSECNET]  [CC IE
Field Configuration Setting] button
• When the master/local module is the LJ71GF11-T2
Project window  [Parameter]  [Network Parameter]  [Ethernet/CC IE Field]  [CC IE Field
Configuration Setting] button
2.
Select the temperature control module in "List of stations" on the CC IE Field Configuration
window.
List of stations
3.
Open the "Parameter Processing of Slave Station" window.
[CC IE Field Configuration]  [Online]  [Parameter Processing of Slave Station]
4.
Set "Method selection" to "Param read (Station parameter)".
110