Mitsubishi Electric NZ2GF2B-60TCTT4 User Manual page 225

Cc-link ie field network temperature control module
Table of Contents

Advertisement

(2) Remote I/O signals, remote registers, and remote buffer memory areas that
can be used
The following table lists the remote I/O signals, remote registers, and remote buffer memory areas that can be
used with this function. (The table below shows the correspondences between the terminals used and the remote
I/O signals/remote registers/remote buffer memory areas.)
Item name
CH Operation monitor
CH Sensor two-point correction offset latch completion
CH Sensor two-point correction gain latch completion
CH Sensor two-point correction offset latch request
CH Sensor two-point correction gain latch request
CH Alert definition
CH Temperature process value (PV)
CH Input range
CH Primary delay digital filter setting
CH Temperature conversion setting
Sensor correction function selection
Cold junction temperature compensation selection
CH Sensor correction value setting
CH Sensor two-point correction offset value (measured
value)
CH Sensor two-point correction offset value (corrected
value)
CH Sensor two-point correction gain value (measured
value)
CH Sensor two-point correction gain value (corrected
value)
Cold junction temperature process value
Control switching monitor
CH Decimal point position
Error code
(3) Setting method
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" windowSelect the temperature control module from "List of
stations"[CC IE Field Configuration][Online][Parameter Processing of Slave Station]
2.
Set "CH Temperature conversion setting".
● When heating-cooling control (expanded mode) or mix control (expanded mode) is selected, "CH Temperature
conversion setting" is ignored.
● When the setting for the Temperature conversion setting is changed from "0: Not used" to "1: Use", temperature
conversion starts. The completion of the first temperature conversion does not turn on CH Operation monitor (RX11 to
RX14).
Remote I/O signal, remote register, remote buffer memory
MT2 (CH2)
MT3 (CH3)
RX12
RX13
RX28
RX2A
RX29
RX2B
RY28
RY2A
RY2B
RY29
RWr5
RWr6
RWr9
RWrA
130H
160H
16DH
13DH
1C2H
1C1H
1E4H
1E9H
281H
282H
288H
28CH
289H
28DH
28AH
28EH
28BH
28FH
600H
602H
621H
622H
A00H
CHAPTER 8 FUNCTIONS
Reference
MT4 (CH4)
RX14
Page 287, Appendix 1.1 (6)
RX2C
Page 293, Appendix 1.1 (14)
RX2D
Page 293, Appendix 1.1 (15)
RY2C
Page 300, Appendix 1.2 (9)
RY2D
Page 300, Appendix 1.2 (10)
RWr7
Page 303, Appendix 2 (5)
RWrB
Page 304, Appendix 2 (6)
190H
Page 312, Appendix 3 (5)
19DH
Page 328, Appendix 3 (16)
1C3H
Page 338, Appendix 3 (29)
Page 341, Appendix 3 (35)
Page 344, Appendix 3 (40)
283H
Page 352, Appendix 3 (51)
290H
Page 352, Appendix 3 (52)
291H
Page 353, Appendix 3 (53)
292H
Page 353, Appendix 3 (54)
293H
Page 354, Appendix 3 (55)
Page 359, Appendix 3 (63)
Page 360, Appendix 3 (65)
623H
Page 362, Appendix 3 (68)
Page 363, Appendix 3 (69)
8
223

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2gf2b-60tcrt4