(9) CH Sensor two-point correction offset latch request (RY28, RY2A, RY2C,
RY2E)
Common
This signal is to request for storing the temperature process value (PV) as a sensor two-point correction offset
value in the following remote buffer memory area.
• CH Sensor two-point correction offset value (measured value) (address: 284H, 288H, 28CH, 290H)
(Page 352, Appendix 3 (52))
For details on the sensor two-point correction function, refer to the following.
Page 133, Section 8.1.5 (2)
(a) Setting range
• OFF: No request
• ON: Latch request
(10)CH Sensor two-point correction gain latch request (RY29, RY2B, RY2D,
RY2F)
Common
This signal is to request for storing the temperature process value (PV) as a sensor two-point correction gain
value in the following remote buffer memory area.
• CH Sensor two-point correction gain value (measured value) (address: 286H, 28AH, 28EH, 292H)
(Page 353, Appendix 3 (54))
For details on the sensor two-point correction function, refer to the following.
Page 133, Section 8.1.5 (2)
(a) Setting range
• OFF: No request
• ON: Latch request