Mitsubishi Electric NZ2GF2B-60TCTT4 User Manual page 144

Cc-link ie field network temperature control module
Table of Contents

Advertisement

A setting of the rate alarm upper limit value and lower limit value to monitor that the temperature process
Ex.
value (PV) is rising within the specified range
Change of
temperature
process value
(PV) (°C)
A setting of the rate alarm upper limit value and lower limit value to monitor that the temperature process
Ex.
value (PV) is falling within the specified range
A setting of the rate alarm upper limit value and lower limit value to monitor that the temperature process
Ex.
value (PV) is changing within the specified range
142
Rate alarm upper limit value
20.0°C
10.0°C
Rate alarm lower limit value
0
Change of
temperature
process value
(PV) (°C)
0
-10.0°C
-20.0°C
Change of
temperature
process value
(PV) (°C)
10.0°C
0
-10.0°C
Rate alarm upper limit value
Rate alarm lower limit value
Rate alarm upper limit value
Rate alarm lower limit value
Time
Time
Time