8.1

Common Functions

This section explains the common functions between the temperature input mode and temperature control mode.
8.1.1

Operation/stop function

Whether to operate or stop the temperature conversion and the temperature control can be set for each channel. By
stopping unused channels, unnecessary disconnection detection or alert output can be prevented.
(1) Setting method
Whether to operate or stop the temperature conversion and the temperature control of each channel can be set
by CH Operation request flag (RY11 to RY14) and CH Stop request flag (RY18 to RY1B). For details, refer to
the following.
• CH Operation request flag (RY11 to RY14) ( Page 296, Appendix 1.2 (4))
• CH Stop request flag (RY18 to RY1B) ( Page 298, Appendix 1.2 (7))
(2) When the check on whether or not the temperature process value is within the
temperature measurement range is unnecessary
Setting CH Stop mode setting (address: 118H, 148H, 178H, 1A8H) to Stop (0) controls error detection. For
details, refer to the following.
Page 336, Appendix 3 (27)
CHAPTER 8 FUNCTIONS
Common
125
8