(51)CH Sensor correction value setting (address: 280H to 283H)
Set the correction value when measured temperature and actual temperature are different.
For details on the sensor correction function, refer to the following.
Page 132, Section 8.1.5
(a) Setting range
• Set the value within the range -5000 to 5000 (-50.00% to 50.00%) of the full scale of the set input range. For
details on the input range, refer to Page 312, Appendix 3 (5).
• When Normal sensor correction (one-point correction) (0H) is set in Sensor correction function selection
(address: 1E4H), the setting content is enabled. (Page 341, Appendix 3 (35))
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default values are set to 0 (0.00%) in all channels.
(52)CH Sensor two-point correction offset value (measured value) (address:
284H, 288H, 28CH, 290H)
The measured value of temperature corresponding to the offset value of the sensor two-point correction is stored
in this remote buffer memory area.
The value to be stored differs depending on the stored value in CH Decimal point position (address: 620H,
621H, 622H, 623H). (Page 362, Appendix 3 (68))
• No decimal place (0): The value is stored as it is.
• One decimal place (1): The value is stored after being multiplied by 10.
For details on the sensor two-point correction function, refer to the following.
Page 133, Section 8.1.5 (2)
(a) Enabling the stored value
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.