Temperature Input Mode - Mitsubishi Electric NZ2GF2B-60TCTT4 User Manual

Cc-link ie field network temperature control module
Table of Contents

Advertisement

8.2

Temperature Input Mode

When using this module as a temperature input module, use this mode.
(1) Setting method
1.
Set "Method selection" to "Param write (Station parameter)".
"CC IE Field Configuration" windowSelect the temperature control module from "List of
stations"[CC IE Field Configuration][Online][Parameter Processing of Slave Station]
2.
Set "100h:Temperature input mode" for "Control mode switching".
(2) Precautions
When resolution is "1", the temperature process value (PV) of the temperature control module is rounded off from
the actual temperature.
When the actual temperature is 1299.5, the temperature process value (PV) of the temperature control
Ex.
module is 1300.
To measure temperature by every 0.1, set resolution to "0.1". (Page 312, Appendix 3 (5))
Note that the temperature process value (PV) is not rounded off for the process alarm and rate alarm.
(Page 140, Section 8.2.1 (1) (d), Page 141, Section 8.2.1 (2) (d))
138
CC-Link IE Field Network
Input from a temperature sensor
Temperature
control module
Master station