Chapter 3 Specifications; General Specifications - Mitsubishi Electric NZ2GF-ETB User Manual

Cc-link ie field network ethernet adapter module
Table of Contents

Advertisement

CHAPTER 3
This chapter describes the specifications of the Ethernet adapter module.
3.1

General Specifications

Item
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
Compliant with
Vibration
JIS B 3502 and
resistance
IEC 61131-2
Shock resistance
Operating
atmosphere
Operating
*1
altitude
Installation location
Overvoltage
*2
category
*3
Pollution degree
Equipment class
*1
Do not use or store the Ethernet adapter module under pressure equivalent to the atmospheric pressure of an elevation
of 0m or higher. Doing so may cause malfunction. When applying pressure to the module, please consult your local
Mitsubishi representative.
*2
This indicates the section of the power supply to which the equipment is assumed to be connected between the public
power distribution network and the machinery within premises.
Category II applies to equipment for which electric power is supplied from fixed facilities. The surge voltage withstand
level for up to the rated voltage of 300V is 2500V.
*3
This index indicates the degree to which conductive material is generated in terms of the environment in which the
equipment is used.
At pollution level 2, only non-conductive pollution occurs. A temporary conductivity caused by condensing must be
expected occasionally.
For compliance with the EMC directive, refer to "EMC and Low Voltage Directives" in this manual. ( Page 231, Appendix
8)
SPECIFICATIONS
5 to 95%RH, non-condensing
Frequency
Under
5 to 8.4Hz
intermittent
8.4 to 150Hz
vibration
5 to 8.4Hz
Under continuous
vibration
8.4 to 150Hz
Compliant with JIS B 3502 and IEC 61131-2 (147m/s
Specification
0 to 55
-25 to 75
Constant
acceleration
2
9.8m/s
2
4.9m/s
2
, 3 times each in X, Y, and Z directions)
No corrosive gases
0 to 2000m
Inside a control panel
II or lower
2 or lower
Class I

CHAPTER 3 SPECIFICATIONS

Half amplitude
Sweep count
3.5mm
10 times each in
X, Y, and Z
directions
1.75mm
3
29

Advertisement

Table of Contents
loading

Table of Contents