On Delay Output Function - Mitsubishi Electric NZ2GF2B-60TCTT4 User Manual

Cc-link ie field network temperature control module
Table of Contents

Advertisement

8.3.14

ON delay output function

This function allows the user to set the delay (response/scan time delay/communication delay) of transistor output.
By setting a delay, and monitoring the ON delay output flag and external output on the program, disconnection of
external output can be determined. The following figure is an example using the ON delay output flag.
Temperature control
module
(1) Setting method
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" windowSelect the temperature control module from "List of
stations"[CC IE Field Configuration][Online][Parameter Processing of Slave Station]
2.
Set a value on "Transistor output monitor ON delay time setting".
(Scan time delay)
Master/local
CPU module
Input module
module
(Communication delay)
Transistor output
Disconnection is checked with
the ON/OFF status of the contact
of the input module and ON
delay output flag.
Sensor ON/OFF status
(Response delay)
External
current
sensor
Heater
CHAPTER 8 FUNCTIONS
Standard
Heating-cooling
183
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2gf2b-60tcrt4

Table of Contents