(b) Immunity requirements
Specifications
EN61000-4-2
Electrostatic discharge immunity
EN61000-4-3
Radiated, radio-frequency,
electromagnetic field immunity
EN61000-4-4
Electrical fast transient/burst
*1
immunity
EN61000-4-5
EN61131-2: 2007
Surge immunity
EN61000-4-6
Immunity to conducted disturbances,
induced by radio-frequency fields
EN61000-4-8
Power-frequency magnetic field
*1
immunity
EN61000-4-11
Voltage dips and interruption
*1
immunity
*1
The module is an open type device (a device designed to be housed in other equipment) and must be installed inside a
conductive control panel. The tests were conducted with the module installed in a control panel.
The accuracy of an analog-digital converter module may temporarily vary within 10%.
*2
(2) Installation in a control panel
The module is open type devices and must be installed inside a control panel.
This ensures safety as well as effective shielding of programmable controller-generated electromagnetic noise.
(a) Control panel
• Use a conductive control panel.
• When securing the top or bottom plate using bolts, cover the grounding part on the control panel so that
the part will not be painted.
• To ensure electrical contact between the inner plate and control panel, take measures such as covering
the bolts so that conductivity can be ensured in the largest possible area.
• Ground the control panel with a thick ground cable so that low impedance can be ensured even at high
frequencies.
• Holes in the control panel must be 10cm diameter or less. A hole with a diameter of 10cm or more may
cause leakage of radio waves. In addition, because radio waves leak through a clearance between the
control panel and its door, reduce the clearance as much as possible. The leakage of radio waves can be
suppressed by the direct application of an EMI gasket on the paint surface.
Our tests have been carried out on a control panel having the attenuation characteristics of 37dB (max.) and
30dB (mean) (measured by 3m method, 30 to 300MHz).
(b) Wiring of power cables and ground cables
• Near the power supply part, provide a ground point to the control panel. Ground the FG terminal with the
thickest and shortest possible ground cable (30cm or shorter).
Test item
Test details
Immunity test in which
electrostatic is applied to the
*1
cabinet of the equipment
Immunity test in which electric
fields are irradiated to the
*1
product
Immunity test in which burst
noise is applied to the power
supply line and signal line
Immunity test in which lightning
surge is applied to the power
*1
supply line and signal line
Immunity test in which high
frequency noise is applied to
*1
the power line and signal line
Immunity test in which the
product is installed in inductive
magnetic field
Immunity test in which power
supply voltage is momentarily
interrupted
Standard value
• 8kV Air discharge
• 4kV Contact discharge
80% AM modulation@1kHz
• 80M-1000MHz: 10V/m
• 1.4G-2.0GHz: 3V/m
• 2.0G-2.7GHz: 1V/m
• AC/DC main power, I/O power, AC I/O (unshielded): 2kV
• DC I/O, analog, communication: 1kV
• AC power line, AC I/O power, AC I/O (unshielded): 2kV
CM, 1kV DM
• DC power line, DC I/O power: 0.5kV CM, DM
*2
• DC I/O, AC I/O (shielded), analog
CM
0.15M-80MHz,
80% AM modulation @1kHz, 10Vrms
50Hz/60Hz, 30A/m
• 0%, 0.5 cycle, starts at zero crossing
• 0%, 250/300 cycle (50/60Hz)
• 40%, 10/12 cycle (50/60Hz)
• 70%, 25/30 cycle (50/60Hz)
APPENDICES
A
, communication: 1kV