(a) Link device assignment
Master station (station No.0)
CPU module
X1000 to X103F
Y1000 to Y103F
W1000 to W100F
W1100 to W111F
236
Master module
Device X
Remote input RX
RX0 to RX3F
Device Y
Remote output RY
RY0 to RY3F
Device W
Remote register RWw
RWw0 to RWwF
Device W
Remote register RWr
RWr0 to RWr1F
Remote device station (station No.1)
Temperature control module
(temperature input mode)
Remote input RX
RX9 Initial data setting completed flag
RXA Error flag
RXB Remote READY
RX11 CH1 Operation monitor
RX12 CH2 Operation monitor
RX13 CH3 Operation monitor
RX18 CH1 Alert occurrence flag
RX0 to RX8, RXC to RX10,
RX14 to RX17, RX19 to RX3F
Remote output RY
RY9 Initial data setting request flag
RYA Error clear request flag
RY10 During operation setting change instruction
RY11 CH1 Operation request flag
RY12 CH2 Operation request flag
RY13 CH3 Operation request flag
RY18 CH1 Stop request flag
RY19 CH2 Stop request flag
RY1A CH3 Stop request flag
RY0 to RY8, RYB to RYF,
RY14 to RY17, RY1B to RY3F
Remote register RWw
RWw0 to RWwF
Remote register RWr
RWr0 Latest error code
RWr1 Error occurrence address
RWr5 CH2 Alert definition
RWr6 CH3 Alert definition
RWr8 CH1 Temperature process value (PV)
RWr9 CH2 Temperature process value (PV)
RWrA CH3 Temperature process value (PV)
RWr2 to RWr4, RWr7,
RWrB to RWr1F