(10)CH Manipulated value (MV) for output with another analog module (RWr18 to
RWr1B)
Standard
another analog module (RWr18 to RWr1B)
cooling (MVc) for output with another analog module (RWr1C to RWr1F)
The values stored in the following remote register areas are converted for other analog modules in the system
(such as a D/A converter module) and stored in these areas.
Remote register area
CH Manipulated value (MV)
CH Manipulated value for
heating (MVh)
CH Manipulated value for
cooling (MVc)
RWr18 to RWr1B are used for heating in the heating-cooling control.
The store range differs depending on the resolution set in the following remote buffer memory area. (0 to 4000/0
to 12000/0 to 16000/0 to 20000)
• Resolution of the manipulated value for output with another analog module (address: 1E8H) (Page 344,
Appendix 3 (39))
For details, refer to the following.
Page 182, Section 8.3.13 (2)
When the device which performs heating or cooling can receive only the analog input, use other analog modules (such as
D/A converter module) to convert the digital output to the analog input.
(11)CH Temperature process value for input with another analog module (PV)
(RWw0 to RWw3)
A digital input value of the current or voltage converted with other analog modules in the system (such as A/D
converter module) can be used as a temperature process value (PV).
Store digital input values of the current or voltage converted with other analog modules (such as A/D converter
module) in this area.
For details, refer to the following.
Page 181, Section 8.3.13 (1)
If a value out of the input range is stored, an error occurs (error code: 002H). A value used for control is fixed to the upper
limit value or lower limit value of the input range.
308
, CH Manipulated value of heating (MVh) for output with
Remote register address
CH1
CH2
RWr10
RWr11
RWr10
RWr11
RWr14
RWr15
Standard
Heating-cooling
, CH Manipulated value of
Heating-cooling
CH3
CH4
RWr12
RWr13
RWr12
RWr13
RWr16
RWr17
Heating-cooling
Reference
Page 303, Appendix 2 (5)