(41)Transistor output monitor ON delay time setting (address: 1EAH)
Set the delay time of the ON delay output flag.
Set this remote buffer memory area to perform the heater disconnection detection with an input module the
system involves.
For ON delay output flag, refer to the following.
Page 293, Appendix 1.1 (16)
For details on the ON delay output function, refer to the following.
Page 183, Section 8.3.14
(a) Setting range
The setting range is 0 or 1 to 50 (10 to 500ms).
When 0 is set, ON delay output flag is not set to 1 (ON).
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default value is set to 0.
(42)CH Process value (PV) scaling function enable/disable setting (address:
200H, 203H, 206H, 209H)
Set enable/disable of the temperature process value (PV) scaling function.
For details on the temperature process value (PV) scaling function, refer to the following.
Page 130, Section 8.1.4
(a) Setting range
• 0: Disable
• 1: Enable
(b) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(c) Default value
The default values are set to Disable (0) in all channels.
Common
APPENDICES
A
Standard
Heating-cooling
345