(b) Setting range
The following table lists set values and setting ranges which are available for alert set values set in each alert
mode.
Setting
value
 (no alert)
0
1
Upper limit input alert
2
Lower limit input alert
3
Upper limit deviation alert
4
Lower limit deviation alert
5
Upper lower limit deviation alert
6
Within-range alert
7
Upper limit input alert with standby
8
Lower limit input alert with standby
9
Upper limit deviation alert with standby
10
Lower limit deviation alert with standby
11
Upper lower limit deviation alert with standby
12
Upper limit deviation alert with standby (second time)
13
Lower limit deviation alert with standby (second time)
14
Upper lower limit deviation alert with standby (second time)
15
Upper limit deviation alert (using the set value (SV))
16
Lower limit deviation alert (using the set value (SV))
17
Upper lower limit deviation alert (using the set value (SV))
18
Within-range alert (using the set value (SV))
19
Upper limit deviation alert with standby (using the set value (SV))
20
Lower limit deviation alert with standby (using the set value (SV))
Upper lower limit deviation alert with standby (using the set value
21
(SV))
Upper limit deviation alert with standby (second time) (using the set
22
value (SV))
Lower limit deviation alert with standby (second time) (using the set
23
value (SV))
Upper lower limit deviation alert with standby (second time) (using
24
the set value (SV))
(c) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
When the set value is out of the range, a write data error (error code: 0004H) occurs, and the temperature
control module operates with the previous set value.
(d) Default value
The default values are set to 0 in all channels.
Alert mode
Setting range of alert set value
Within the temperature measurement range of the set input range
(Page 312, Appendix 3 (5))
(-(full scale)) to full scale
0 to full scale
Within the temperature measurement range of the set input range
(Page 312, Appendix 3 (5))
(-(full scale)) to full scale
0 to full scale
(-(full scale)) to full scale
0 to full scale
(-(full scale)) to full scale
0 to full scale
(-(full scale)) to full scale
0 to full scale
(-(full scale)) to full scale
0 to full scale
APPENDICES
A