(53)CH Sensor two-point correction offset value (corrected value) (address:
285H, 289H, 28DH, 291H)
Set the temperature of the offset value of the sensor two-point correction.
For details on the sensor two-point correction function, refer to the following.
Page 133, Section 8.1.5 (2)
(a) Setting range
The setting range is identical to the temperature measurement range of the set input range. (Page 312,
Appendix 3 (5))
(b) Setting unit
The value to be set differs depending on the stored value in CH Decimal point position (address: 620H,
621H, 622H, 623H). (Page 362, Appendix 3 (68))
• No decimal place (0): Set a value in 1 ( or digit) unit.
• One decimal place (1): Set a value in 0.1 () unit (tenfold value).
(c) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(d) Default value
The default values are set to 0 in all channels.
(54)CH Sensor two-point correction gain value (measured value) (address: 286H,
28AH, 28EH, 292H)
The measured value of temperature corresponding to the gain value of the sensor two-point correction is stored
in this remote buffer memory area.
The value to be stored differs depending on the stored value in CH Decimal point position (address: 620H,
621H, 622H, 623H). (Page 362, Appendix 3 (68))
• No decimal place (0): The value is stored as it is.
• One decimal place (1): The value is stored after being multiplied by 10.
For details on the sensor two-point correction function, refer to the following.
Page 133, Section 8.1.5 (2)
(a) Enabling the stored value
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
Common
Common
APPENDICES
A
353