(27)CH Stop mode setting (address: 118H, 148H, 178H, 1A8H)
Set the mode when PID control stops.
(a) Setting range and action of the temperature control module
The following table lists the relationship.
Stop mode
Stop
0
Monitor
1
Alert
2
: Executed, : Not executed
*1
*2
Means that the temperature control module checks whether the input temperature is in the temperature measurement
range set in the input range.
For details on the operation shown above, refer to the following.
• PID control: Page 153, Section 8.3.3 (5)
• Temperature judgment: Page 303, Appendix 2 (5)
• Alert judgment: Page 169, Section 8.3.11
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default value depends on the mode used.
• Temperature input mode: Stop (0) in all channels.
• Temperature control mode: Monitor (1) in all channels.