(c) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(d) Default value
A default value differs depending on modules to be used.
Remote buffer memory
CH Upper limit setting limiter (address: 10AH, 13AH, 16AH, 19AH)
CH Lower limit setting limiter (address: 10BH, 13BH, 16BH, 19BH)
(15)CH Control output cycle setting (address: 10CH, 13CH, 16CH, 19CH)
CH Heating control output cycle setting (address: 10CH, 13CH, 16CH, 19CH)
, CH Cooling control output cycle setting (address: 1C6H, 1CBH, 1D0H,
Heating-cooling
1D5H)
Heating-cooling
Set the pulse cycle (ON/OFF cycle) of the transistor output. In the heating-cooling control, the output cycle of the
heating control and cooling control can be set individually. 10CH, 13CH, 16CH, and 19CH are used for heating in
the heating-cooling control.
The ON time of the control output cycle is determined by multiplying the control output cycle by the manipulated
*1
value (MV)
(%) calculated by PID operation. If the manipulated value (MV)
cycle is output repeatedly.
*1
For the heating control output cycle, the manipulated value for heating (MVh) is used. For the cooling control output
cycle, manipulated value for cooling (MVc) is used.
When 700 (70%) is stored in CH Manipulated value (MV) (RWr10 to RWr13) and 100 (100s) is set to
Ex.
CH Control output cycle setting (address: 10CH, 13CH, 16CH, 19CH)
The following calculation shows that the transistor output turns on for 70s and off for 30s per 100s.
• 100s  0.7 (70%) = 70s (ON time is 70s.)
Transistor
OFF
output
326
OFF
Transistor output
Control output cycle
100s
ON
Manipulated value
(MV)(70%)
70s
NZ2GF2B-60TCTT4
1300
0
Manipulated value
(MV) (%)
ON
Control output cycle
Control output cycle
100s
Manipulated value
(MV)(70%)
70s
Default value
NZ2GF2B-60TCRT4
6000
-2000
*1
is constant, a pulse of the same
Control output cycle
100s
Manipulated value
(MV)(70%)
70s
,
Standard