8.3.9
Derivative action selection function
A derivative action appropriate for each of fixed value action and ramp action can be selected and the action
characteristic can be improved using this function.
(1) Action
Each type of derivative action operates as shown below.
CH Derivative action
selection (address: 110H,
140H, 170H, 1A0H)
Measured value derivation (0)
Deviation derivation (1)
(2) Setting method
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" windowSelect the temperature control module from "List of
stations"[CC IE Field Configuration][Online][Parameter Processing of Slave Station]
2.
Set "CH Differentiation operation selection".
166
Fixed value action
Disturbance
Fixed value action
Disturbance
Action
Ramp action
Set value (SV)
Temperature
process value
(PV)
Ramp action
Set value (SV)
Temperature
process value
(PV)
Heating-cooling
Standard
This setting effectively
prevents the temperature from
being affected by disturbance,
though the performance to
follow the set value can be
low.
This setting allows the
temperature to follow the set
value well, though the
disturbance effect is great.