7.2

SIO Mode Function

Channels 1 to 8 of the IO-Link module can be used for the IO-Link mode as well as the SIO mode where a maximum of 16
signals can be used.
For each channel, set either the IO-Link mode or SIO mode.
The default setting of each channel is the SIO mode input, but can be changed to the SIO mode input.
In the SIO mode, each channel works as the source type, therefore it cannot be used as the sink type.
For the operation of the IO-Link module that is disconnected from CC-Link IE Field Network during the SIO
mode, refer to the following.
Page 93 Output HOLD/CLEAR setting function

SIO input function

The ON/OFF status (X signal) of inputs is notified to Remote input (RX) of the CC-Link IE Field Network.
To operate the SIO mode for inputs, turn off Channel n (CQ/Q) I/O switching command (RY10 to RY1F) in the initial
processing.
To apply the I/O switching setting changed in processing other than the initial processing and parameter setting on an
engineering tool, turn on Operation condition setting request flag (RWw0.b9).
Setting procedure
1.
Open the "CC IE Field Configuration" window.
For the master/local module RJ71GF11-T2
[Navigation window]  [Parameter]  [Module Information]  [RJ71GF11-T2]  [Module Parameter]  [Basic Settings]
 [Network Configuration Settings]
2.
Open the "Parameter Processing of Slave Station" window.
From the list of stations, select an IO-Link module  [CC IE Field Configuration]  [Online]  [Parameter Processing of
Slave Station].
3.
Set "Method selection" to "Parameter Write".
4.
For each channel, set "Write Value" of "Pin configuration setting" to "INPUT".
7 FUNCTIONS
75
7.2 SIO Mode Function
7