Parameter Group 4-** Auto-Start/Stop - Danfoss VLT MCD 600 Operating Manual

Soft starter
Hide thumbs Also See for VLT MCD 600:
Table of Contents

Advertisement

VLT® Soft Starter MCD 600
Operating Guide
Table 73: 3-19 - Brake Current Limit-2
Range
*250%
100–600% FLC
Table 74: 3-20 - Soft Brake Delay-2
Range
Function
*400 ms
400–2000
Sets the time which the soft starter waits after a stop signal is received, before it begins to supply brak-
ms
ing current to the motor. Set to allow time for K1 and K2 to switch.

10.8 Parameter Group 4-** Auto-Start/Stop

Table 75: 4-1 - Auto-Start/Stop Mode
Option
*
Disable
Enable Clock Mode
Enable Timer Mode
Table 76: 4-2 - Run Time
Range
*00:00
00:00–23:59 hh:mm
Table 77: 4-3 - Stopped Time
Range
*00:00
00:00–23:59 hh:mm
Table 78: 4-4 - Sunday Mode
Option
Function
Enables or disables auto-start/stop for Sunday.
*
Start/Stop Disable
Disables auto-start/stop control. Any times scheduled in parameter 4-5 Sunday Start Time or parameter
4-6 Sunday Stop Time are ignored.
Start Only Enable
Enables auto-start control. Any auto-stop times scheduled in parameter 4-6 Sunday Stop Time are ignor-
ed.
Stop Only Enable
Enables auto-stop control. Any auto-start times scheduled in parameter 4-5 Sunday Start Time are ignor-
ed.
Start/Stop Enable
Enables auto-start and auto-stop control.
Table 79: 4-5 - Sunday Start Time
Range
*00:00
00:00–23:59
Danfoss A/S © 2020.12
Function
Sets the current limit for soft brake.
Function
Enable or disable auto-start/stop operation.
Function
Sets the duration for the soft starter to run after a timer mode auto-start.
Function
Sets the duration for the soft starter to remain stopped when operating in timer mode.
Function
Sets the auto-start time for Sunday (24-hour format).
Programmable Parameters
AQ262141844215en-000401 / 175R1174 | 89