VLT® Soft Starter MCD 600
Operating Guide
-
Parameter 5-13 Overpower.
-
Parameter 5-14 Overpower Delay.
-
Parameter 6-9 Overpower.
11.2.37 Overvoltage
Cause
There has been a voltage surge on the mains. Causes can include problems with a transformer tap regulator or off-loading of a large
transformer load.
Troubleshooting
Check the following parameters:
-
Parameter 5-9 Overvoltage.
-
Parameter 5-10 Overvoltage Delay.
-
Parameter 6-7 Overvoltage.
11.2.38 Parameter Out of Range
Cause
This trip is not adjustable.
A parameter value is outside the valid range. The LCP indicates the first invalid parameter.
An error occurred loading data from the EEPROM to RAM when the LCP powered up.
The parameter set or values in the LCP do not match the parameters in the soft starter.
Load User Set has been selected but no saved file is available.
Troubleshooting
Reset the fault. The soft starter loads the default settings.
If the problem persists, contact the local distributor.
There are no parameters related to this trip message.
11.2.39 Phase Sequence
Cause
The phase sequence on the soft starter mains terminals (L1, L2, L3) is not valid.
Troubleshooting
Check the phase sequence on L1, L2, and L3, and ensure that the setting in parameter 5-18 Phase Sequence is suitable for the
installation.
Check the following parameters:
-
Parameter 5-18 Phase Sequence.
-
Parameter 6-16 Phase Sequence.
11.2.40 Power Loss
Cause
This trip is not adjustable. The soft starter is not receiving mains supply on 1 or more phases.
Troubleshooting
Check that the main contactor closes when a start command is given and remains closed until the end of a soft stop.
Check the fuses. If testing the soft starter with a small motor, it must draw at least 10% of the programmed FLC setting on each
phase.
If shunt relay mode is enabled (parameter 20-8 Shunt Trip Mode), certain trips may cause the shunt relay to open the circuit
breaker.
There are no parameters related to this trip message.
11.2.41 Pressure Sensor
Cause
The smart card has detected a fault with the pressure sensor.
126 | Danfoss A/S © 2020.12
Troubleshooting
AQ262141844215en-000401 / 175R1174