Ground Terminations; Typical Installations; Internally Bypassed Installation - Danfoss VLT MCD 600 Operating Manual

Soft starter
Hide thumbs Also See for VLT MCD 600:
Table of Contents

Advertisement

VLT® Soft Starter MCD 600
Operating Guide
F1
K1
Illustration 16: Wiring of Inside Delta Installation, Externally Bypassed
K1
Main contactor
K2
Bypass contactor (external)
F1
Fuses or circuit breaker

5.9.5 Ground Terminations

Models MCD6-0654B~MCD6-1250B/MCD6-0590C~MCD6-1134C have a ground terminal on each side of the soft starter, near the
top back corner. Either grounding point may be used.
Models MCD6-0020B~MCD6-0579B/MCD6-0160C~MCD6-0448C do not require a protective earth connection. All internal conduc-
tive parts are fully enclosed by a non-conductive outer case.

5.10 Typical Installations

5.10.1 Internally Bypassed Installation

The VLT® Soft Starter MCD 600 is installed with a main contactor (AC3-rated). Control voltage must be supplied from the input side
of the contactor.
The main contactor is controlled by the main contactor output (13, 14).
42 | Danfoss A/S © 2020.12
K2
1/L1
T1B
3/L2
T2B
5/L3
T3B
E
13
14
K1
03
04
K2
13, 14
03, 04
2/T1
U1(1) U2(4)
4/T2
V1(2)
W1(3)
6/T3
Main contactor output
Bypass contactor output
AQ262141844215en-000401 / 175R1174
Installation
M
V2(5)
3
W2(6)