Parameter Group 11-** Pump Clean - Danfoss VLT MCD 600 Operating Manual

Soft starter
Hide thumbs Also See for VLT MCD 600:
Table of Contents

Advertisement

VLT® Soft Starter MCD 600
Operating Guide
Table 172: 10-12 - User Parameter 5
Option
Function
Selects which information is shown on the programmable monitoring screen.
See parameter 10-10 User Parameter 3 for details.
*
Motor Power
See parameter 10-10 User Parameter 3 for details.
Table 173: 10-13 - User Parameter 6
Option
*
Motor Temp (%)

10.15 Parameter Group 11-** Pump Clean

Table 174: 11-1 - Reverse Torque
Range
* 20%
20–100%
Table 175: 11-2 - Reverse Time
Range
* 10 s
0:00–1:00 (minutes:seconds)
Table 176: 11-3 - Forward Current Limit
Range
*100%
100–600% FLC
Table 177: 11-4 - Forward Time
Range
* 10 s
0:00–1:00 (minutes:sec-
onds)
Table 178: 11-5 - Pump Stop Mode
Option
*
Coast To Stop
TVR Soft Stop
Table 179: 11-6 - Pump Stop Time
Range
* 10 s
0:00–1:00 (minutes:seconds)
110 | Danfoss A/S © 2020.12
Function
Selects which information is shown on the programmable monitoring screen.
See parameter 10-10 User Parameter 3 for details.
See parameter 10-10 User Parameter 3 for details.
Function
Sets the torque level for reverse jog operation during pump clean.
Function
Sets the time for the starter to operate in reverse jog during a pump clean cycle.
Function
Sets the current limit for forward start operation during pump clean.
Function
Sets the time for the soft starter to run the motor after a forward start during a pump clean
cycle.
Function
Selects the stop mode for pump clean.
Function
Sets the stopping time for the starter during a pump clean cycle.
Programmable Parameters