VLT® Soft Starter MCD 600
Operating Guide
Real-time line current on each phase.
Last start information.
Date and time.
1
69.0 A
2
Last start
3
350% FLC
Illustration 28: Operating Feedback Screens
1
Motor running current
2
Start duration (seconds)

8.5.4 Performance Graph

The performance graph provides a real-time display of operating performance. Use parameters 10-2 to 10-5 to format the graph.
The display on the main LCP shows information for motor current.
000.0 A
If a remote LCP is connected, press [Graph] to change the graph data. The graph can show:
Motor current.
Motor temperature.
Motor power factor.
Analog input data from the smart card (if installed).
Danfoss A/S © 2020.12
010s
4
D Temp 5%
0-400%
3
Maximum start current drawn (as a percentage of
motor full load current)
4
Calculated rise in motor temperature
AQ262141844215en-000401 / 175R1174 | 59