Table 134: 6-19 - Shorted SCR Action
Option
*
3-phase Control Only
PowerThrough
Trip+Shunt Relay
For more details on PowerThrough operation, see
Table 135: 6-20 - Battery/Clock
Option
*
Soft Trip and Log
Soft Trip and Reset
Trip Starter
Trip and Reset
Warn and Log
Log Only
Trip+Shunt Relay

10.11 Parameter Group 7-** Inputs

Table 136: 7-1 - Input A Function
Option
Command Override:
Network
Command Override:
Digital
Command Override:
Keypad
*
Input Trip (N/O)
Input Trip (N/C)
100 | Danfoss A/S © 2020.12
Function
Function
Selects whether the soft starter allows PowerThrough operation, if the soft starter is damaged on 1
phase. The soft starter uses 2-phase control, allowing the motor to continue operating in critical ap-
plications.
9.4
PowerThrough.
Function
Selects the soft starter's response to the protection event.
Function
Selects the function of Input A.
Overrides the setting of parameter 1-1 Command Source and sets the command source to the com-
munications network.
Overrides the setting of parameter 1-1 Command Source and sets the command source to the digital
inputs.
Overrides the setting of parameter 1-1 Command Source and sets the command source to the re-
mote LCP.
A closed circuit across DI-A, COM+ trips the soft starter.
An open circuit across DI-A, COM+ trips the soft starter.
Programmable Parameters
AQ262141844215en-000401 / 175R1174