VLT® Soft Starter MCD 600
Operating Guide
For duty/standby applications, set parameter 6-17 Motor Overtemperature to Log Only and install temperature protection for each
motor.
To use the secondary motor set, set a programmable input to Motor Set Select. The input must be closed when a start command is
given (see parameter 7-1 Input A Function and parameter 7-5 Input B Function). The soft starter checks which motor set to use at start
and uses that motor set for the entire start/stop cycle.
The soft starter uses the secondary motor settings to control a start when instructed via a programmable input (see parameter 7-1
Input A Function and parameter 7-5 Input B Function).
Danfoss A/S © 2020.12
N O T I C E
Operation
AQ262141844215en-000401 / 175R1174 | 73