Danfoss VLT MCD 600 Operating Manual page 89

Soft starter
Hide thumbs Also See for VLT MCD 600:
Table of Contents

Advertisement

VLT® Soft Starter MCD 600
Operating Guide
Table 44: 2-8 - Jog Torque
Range
Function
* 50%
20–100%
The VLT® Soft Starter MCD 600 can jog the motor at a reduced speed, which allows precise positioning of
belts and flywheels. Jog can be used for either forward or reverse operation.
Set the current limit for jog operation.
Table 45: 2-9 - Stop Mode
Option
Coast To Stop
*
TVR Soft Stop
Adaptive Control
DC Brake
Soft Brake
Table 46: 2-10 - Stop Time
Range
* 0 s
0:00–4:00 (mi-
nutes:seconds)
Table 47: 2-11 - Adaptive Stop Profile
Option
Early Deceleration
*
Constant Deceleration
Late Deceleration
Table 48: 2-12 - Adaptive Control Gain
Range
Function
* 75%
1–200%
Adjusts the performance of adaptive control. This setting affects both starting and stopping control.
Table 49: 2-13 - Multi Pump
Option
Function
Adjusts the performance of adaptive control to suit installations with multiple pumps connected to a com-
mon outlet manifold.
*
Single Pump
Manifold Pump
Danfoss A/S © 2020.12
Function
Sets the time for soft stopping the motor using TVR or adaptive control. If a main contactor is instal-
led, the contactor must remain closed until the end of the stop time. Use the main contactor output
(13, 14) to control the main contactor.
Function
Selects which profile the VLT® Soft Starter MCD 600 uses for an adaptive control soft stop.
Function
Selects the stop mode.
AQ262141844215en-000401 / 175R1174 | 85