Danfoss VLT MCD 600 Operating Manual page 92

Soft starter
Hide thumbs Also See for VLT MCD 600:
Table of Contents

Advertisement

VLT® Soft Starter MCD 600
Operating Guide
Option
DC Brake
Soft Brake
Table 66: 3-12 - Stop Time-2
Range
*0 s
0:00–4:00 (mi-
nutes:seconds)
Table 67: 3-13 - Adaptive Stop Profile-2
Option
Early Deceleration
*
Constant Deceleration
Late Deceleration
Table 68: 3-14 - Adaptive Control Gain-2
Range
*75%
1–200%
Table 69: 3-15 - Multi Pump-2
Option
Function
Adjusts the performance of adaptive control to suit installations with multiple pumps connected to a com-
mon outlet manifold.
*
Single Pump
Manifold Pump
Table 70: 3-16 - Start Delay-2
Range
* 0 s
0:00–60:00 (minutes:seconds)
Table 71: 3-17 - DC Brake Torque-2
Range
*20%
20–100%
Table 72: 3-18 - DC Brake Time-2
Range
*1 s
0:01–0:30 (minutes:seconds)
88 | Danfoss A/S © 2020.12
Function
Sets the time for soft stopping the motor using TVR or adaptive control. If a main contactor is instal-
led, the contactor must remain closed until the end of the stop time. Use the main contactor output
(13, 14) to control the main contactor.
Function
Selects which profile the soft starter uses for an adaptive control soft stop.
Function
Adjusts the performance of adaptive control.
This setting affects both starting and stopping control.
Function
Sets a delay after the starter receives a start command before it starts the motor.
Function
Sets the amount of brake torque the soft starter uses to slow the motor.
Function
Sets the duration for DC injection during a braking stop.
Function
Programmable Parameters
AQ262141844215en-000401 / 175R1174