Danfoss VLT MCD 600 Operating Manual page 97

Soft starter
Hide thumbs Also See for VLT MCD 600:
Table of Contents

Advertisement

VLT® Soft Starter MCD 600
Operating Guide
Table 103: 5-6 - Overcurrent Delay
Range
* 0 s
0:00–1:00 (minutes:seconds)
Table 104: 5-7 - Undervoltage
Range
Function
*350
100–1200 V
Sets the trip point for undervoltage protection. Set as required.
Table 105: 5-8 - Undervoltage Delay
Range
* 1 s
0:01–1:00 (minutes:seconds)
Table 106: 5-9 - Overvoltage
Range
*500
100–1500 V
Table 107: 5-10 - Overvoltage Delay
Range
* 1 s
0:01–1:00 (minutes:seconds)
Table 108: 5-11 - Underpower
Range
*10%
10–120%
Table 109: 5-12 - Underpower Delay
Range
*1 s
0:01–1:00 (minutes:seconds)
Table 110: 5-13 - Overpower
Range
*150%
80–200%
Table 111: 5-14 - Overpower Delay
Range
* 1 s
0:01–1:00 (minutes:seconds)
Danfoss A/S © 2020.12
Function
Slows the soft starter's response to overcurrent, avoiding trips due to momentary overcur-
rent events.
Voltage protection does not operate correctly until the soft starter is in Run mode.
Function
Slows the soft starter's response to undervoltage, avoiding trips due to momentary fluctua-
tions.
Function
Sets the trip point for overvoltage protection. Set as required.
Function
Slows the soft starter's response to overvoltage, avoiding trips due to momentary fluctua-
tions.
Function
Sets the trip point for underpower protection. Set as required.
Function
Slows the soft starter's response to underpower, avoiding trips due to momentary fluctua-
tions.
Function
Sets the trip point for overpower protection. Set as required.
Function
Slows the soft starter's response to overpower, avoiding trips due to momentary fluctua-
tions.
N O T I C E
AQ262141844215en-000401 / 175R1174 | 93
Programmable Parameters