Danfoss VLT MCD 600 Operating Manual page 81

Soft starter
Hide thumbs Also See for VLT MCD 600:
Table of Contents

Advertisement

VLT® Soft Starter MCD 600
Operating Guide
Parameter group number
5-5
5-6
5-7
5-8
5-9
5-10
5-11
5-12
5-13
5-14
5-15
5-16
5-17
5-18
6
6-1
6-2
6-3
6-4
6-5
6-6
6-7
6-8
6-9
6-10
6-11
6-12
6-13
6-14
6-15
6-16
6-17
Danfoss A/S © 2020.12
Parameter group name
Overcurrent
Overcurrent Delay
Undervoltage
Undervoltage Delay
Overvoltage
Overvoltage Delay
Underpower
Underpower Delay
Overpower
Overpower Delay
Excess Start Time
Restart Delay
Starts per Hour
Phase Sequence
Protection Actions
Auto-Reset Count
Auto-Reset Delay
Current Imbalance
Undercurrent
Overcurrent
Undervoltage
Overvoltage
Underpower
Overpower
Excess Start Time
Input A Trip
Input B Trip
Network Communications
Remote Keypad Fault
Frequency
Phase Sequence
Motor Overtemperature
Programmable Parameters
Default setting
400%
00:00 (mm:ss)
350 V
00:01 (mm:ss)
500 V
00:01 (mm:ss)
10%
00:01 (mm:ss)
150%
00:01 (mm:ss)
00:20 (mm:ss)
00:10 (mm:ss)
0
Any Sequence
0
00:05 (mm:ss)
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Log Only
Log Only
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Soft Trp and Log
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
AQ262141844215en-000401 / 175R1174 | 77