Com2 Settings - MB Connect Line mbNET.rokey RKH 210 Manual

Hide thumbs Also See for mbNET.rokey RKH 210:
Table of Contents

Advertisement

• VCOM LAN2 (PC adapter in the SIMATIC Manager)
• RFC1006
• mbNETS7 driver (installable directly in the SIMATIC Manager)

25.3.1 COM2 Settings

Protocol: MPI/PROFIBUS Network Driver
The Protocol Choice MPI/PROFIBUS network driver requires the installation of a network driver on the
client PC beforehand! Only in conjunction with the option RFC1006 can a separate driver installation be
dispensed with and the "TCP/IP (Auto)" option under the PG/PC interface used. RFC1006 uses TCP port
102.
Designation
Protocol
Enable RFC1006 pro-
tocol
own
station address
With this station address, the connected routers in the MPI/DP network logs on. This is necessary if the
communication is exclusively via RFC1006. In a mixed operation of connections with network drivers and
RFC1006, the router always logs in using the address specified in the first connection used.
Enable routing via
RFC1006
Page 162 von 324 | V 7.2.0 - en | Aug 25
NO T I CE
Description
Protocol selection field. You can choose between a connection via MPI/Profibus
network driver or VCOM LAN2/PC adapter.
Check box for enabling/disabling this function.
If RFC1006 is enabled, enter a unique MPI/DP station address for the router (mb-
NET).
NO T I C E
Check box for enabling/disabling this function.
The activated function enables routing via RFC1006.
th
, 2022 |