AC and DC Current Load

Table 3-7 Typical Power Loads and Heat Dissipation Values - Expansion Cabinet 800 MHz
Configuration (Continued)
Expansion
Cabinet
Consumptions
MTS 800 MHz
Configuration
TETRA TX 25 W and TEDS TX 10 W
MTS4 with 1 BR w.
MTCC
MTS4 with 2 BRs w.
MTCC
MTS4 with 3 BRs w.
MTCC
MTS4 with 4 BRs w.
MTCC
AC and DC Current Load

Backup Battery

The backup battery is normally located near the cabinet(s). The recommended batteries to be used are
a VRLA (Valve Regulated Lead Acid) recombination type, with -48 VDC nominal.
3-20
Heat
AC
AC
(W)
(W)
405
380
700
650
1130
1055
1445
1345
• All the values in the table are calculated from AC = 230 V
• Add additional 5% for 110 V
• Charging is up to 6 A per PSU
The MTS has a certain power consumption even when the Power Supply Unit
(PSU) is switched off (0.1 A @ -48 VDC, 0.04 A @ 110 VAC, 0.02 A @ 240 VAC).
The switch only disconnects DC outputs and charging currents. In case of
field repair, all PSU connecting cables have to be disconnected.
AC
Heat AC
When
When
Charg-
Charging
ing (W)
(W)
790
455
1085
740
1890
1215
2205
1515
Chapter 3: Site Preparation
DC
Heat
-48 V
DC
(W)
(W)
Comment
395
370
High power PA,
fans
685
635
High power PA,
fans
1105
1030
High power PA,
fans
1410
1310
High power PA,
fans
6802800U74-N September 2009