Measurement Commands; Advanced Operating Commands - R&S NGE100B User Manual

Hide thumbs Also See for NGE100B:
Table of Contents

Advertisement

®
R&S
NGE100B

7.4 Measurement commands

The MEASure subsystem provides commands to query the voltage and current values
of a channel.
MEASure[:SCALar]:CURRent[:DC]?
This command queries the measured current value of the previous selected channel.
Return values:
<Current>
Example:
Usage:
MEASure[:SCALar]:POWer?
This command queries the measured power value of the previous selected channel.
Return values:
<Power>
Example:
Usage:
MEASure[:SCALar][:VOLTage][:DC]?
This command queries the measured voltage value of the previous selected channel.
Return values:
<Voltage>
Example:
Usage:

7.5 Advanced operating commands

The following shows the subsystem that contains the commands for configuring the
arbitrary function, EasyRamp and Digital I/O functions.
User Manual 5601.1343.02 ─ 09
<numeric_value>
Return the measured current.
Default unit: A
MEAS:CURR? -> 1.000
Query only
<Numeric_value>
Return the measured power value.
Default unit: W
MEAS:POW? -> 3.00E+00
Return the measured power value of the selected channel.
Query only
<numeric_value>
Return the measured voltage.
Default unit: V
MEAS? -> 1.000E+00
Query only
Remote control commands
Advanced operating commands
93

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nge102bNge103b

Table of Contents