Smartgen HGM7110DC User Manual page 38

Dc genset controller
Table of Contents

Advertisement

No.
Items
Open Circuit
2
Action
High
Temp.
3
Shutdown
High
Temp.
4
Warn
Low
Temp.
5
Warn
Oil Pressure Sensor
1
Curve Type
Open
Circuit
2
Action
Low
OP
3
Shutdown
4
Low OP Warn
Liquid Level Sensor
1
Curve Type
Open
Circuit
2
Action
Low
Level
3
Warn
Configure Sensor 1
Configure
1
Sensor
Setting
Configure Sensor 2
Configure
1
Sensor
Setting
HGM7110DC Genset Controller
Parameters
(0-2)
(-50-+300)º C
(-50-+300)º C
(0-1)
(0-15)
(0-2)
(0-1000)kPa
(0-1000)kPa
(0-15)
(0-2)
(0-300)%
1
(0-1)
2
(0-1)
Version: 1.0
Defaults
0: Warn; 1: Shutdown;
0
2: No action
Shutdown when sensor temperature
higher than this value. Detecting only
98
after safety delay is over. The delay
value can be set.
Warn when sensor temperature higher
than this value. Detecting only after
95
safety delay is over. The delay value
and return value can be set.
0
0: Disable; 1: Enable
7
SGX
0: Warn 1: Shutdown
0
2: No action
Shutdown when oil pressure lower
than this value. Detecting only after
103
safety delay is over. The delay value
can be set.
Warn when oil pressure higher than
this value. Detecting only after safety
124
delay is over. The delay value and
return value can be set.
4
SGH。See form 5
0:Warn; 1:Shutdown;
0
2:No action
Warn when level lower than this value.
10
It is detecting all the time. The delay
value and return value can be set.
0: Disable 1: Enable; (can be set as
0
temperature/pressure/liquid
sensor).
0: Disable; 1: Enable; (can be set as
0
temperature/pressure/liquid
sensor).
2014-09-27
HGM7110DC Genset Controller
Description
See form 5.